U175 cooling water cycle
DE EN
LabWatch 146
is a Web LIOB-580 modul from Loytec
Room: U175/ Lüftungszentrale / Tel. 061 207 3797/3665/3824
Adress: 10.34.108.146
Name: http://phys-alarm-06.physik.p.unibas.ch
LWEB-146:
Warning message:
Email to | Roland Steiner, Laurent Marot, Rejaul SK,On-call duty (Pikettdienst) |
Email to | Roland Steiner, Laurent Marot, Rejaul SK, On-call duty (Pikettdienst) |
SMS to | Laurent Marot, Rejaul SK,HW+Stv, On-call duty (Pikettdienst) |
This module is monitoring the pressures of the cooling water cycle in the lab U175. It measures the pressure in the flow line (german: “Vorlauf”, VL) and the return line (german: “Rücklauf”, RL) and calculates the difference.
If the return line pressure falls below 0.6 bar, the Apaco station will shut down. To avoid this situation, a warning message is sent to techalarm-phys@unibas.ch by email if the RL is lower than 1.1 bar. From this email account, the email is forwarded to the responsible staff.
Absender: | LabWatch-146 / Raum U175 |
Subject : | RL-Druck zu tief / U175 Apaco-Station |
RL= <ist_wert> Water pressure in room U175 of the return line is lower than <soll_wert> bar Water should be refilled soon. {timestamp} https://labwatch.physik.unibas.ch/labwatch/146 |
|
Alarm Clear Subject : | RL-Druck Cleared / U175 Apaco-Station |
Water pressure in room U175 of the return line exceeded bar and is in the normal range again. {timestamp} |
If the flow line pressure (VL) drops below 4.5 bar, the pump could have failed. A warning message is sent to techalarm-phys@unibas.ch by email and forwarded to the responsible staff.
Absender: | LabWatch-146 / Raum U175 |
Subject : | VL-Druck zu tief / U175 Apaco-Station |
Water pressure in room U175 of the flow line (VL) drops below 4.5 bar
Possible cause: pump failure. https://labwatch.physik.unibas.ch/labwatch/146 |
|
Alarm Clear Subject : | VL-Druck Cleared / U175 Apaco-Station |
Water pressure in room U175 of the flow line (VL) exceeded 4.5 bar
and is in the normal range again. {timestamp} |
If the RL pressure keeps dropping below 0.9 bar, both an acoustic and an optical alarm will be triggered. The alarm can be silenced for an interval of 60 minutes. The same action will take effect if the pressure difference goes below or above its limits. An alarm message is sent to techalarm-phys@unibas.ch by email and forwarded to the responsible staff.
Absender: | LabWatch-146 / Raum U175 |
Subject : | Alarm / U175 Apaco-Station |
Water pressure of return line in room U175 is lower than <soll_wert> bar Below 0.6 bar, the cooling water unit will be shut down. {timestamp} https://labwatch.physik.unibas.ch/labwatch/146
|
If the pressure difference is below or above its limits, a warning message is sent to techalarm-phys@unibas.ch by email and forwarded to the responsible staff
Absender: | LabWatch-146 / Raum U175 |
Subject : | Alarm / U175 Apaco-Station |
The pressure difference in room U175 between flow line and return line is lower than <soll_wert> bar. <{timestamp} https://labwatch.physik.unibas.ch/labwatch/146 |
|
Alarm Clear Subject : | Alarm Cleared / U175 Apaco-Station |
The pressure difference in room U175 between flow line and return line exceeds <soll_wert> bar and is in the normal range again. {timestamp} |
Absender: | LabWatch-146 / Raum U175 |
Subject : | Alarm / U175 Apaco-Station |
The pressure difference in room U175 between flow line and return line exceeds <soll_wert> bar {timestamp} https://labwatch.physik.unibas.ch/labwatch/146 |
|
Alarm Clear Subject : | Alarm Cleared / U175 Apaco-Station |
The pressure difference in room U175 between flow line and return line is below <soll_wert> bar and is in the normal range again. {timestamp} |
Absender: | LabWatch-146 / Raum U175 |
Subject : | Alarm Quitt / U175 Apaco Station |
The acknowledgment key was pressed on location! |
Normalrange
- RL-pressure 1.20 bar
- VL-pressure 5.12 bar
Threshold values for warning message:
- return line pressure RL < 1.1 bar
- flow line pressure VL < 5.0 bar
- return line pressure RL < 0.8 bar
- pressure difference < 0.7 bar
- pressure difference > 4.5 bar
- Trigger delay time = 10 sec
- ReAlarm time = 60 min