U163 Oxygen concentration monitoring
DE  EN

LabWatch 161

is a Web-IO 2xDigital In, 2xDigital Out from WuT #57637



LabWatch-145
Room:  O305 / AFM-Labor / Tel.: 061 207 37 32

Adresse:  10.34.108.161
Name:     http://phys-alarm-21.physik.p.unibas.ch/

Warning message:
Email to Urs Gysin, Marcin Kisiel, Yves Pellmont, Alexina Ollier, On-call duty (Pikettdienst)
SMS  to

Alarm:
Email to Urs Gysin, Marcin Kisiel, Yves Pellmont, Alexina Ollier, On-call duty (Pikettdienst)
SMS  to Urs Gysin, Marcin Kisiel, Yves Pellmont, HW+Stv, On-call duty (Pikettdienst)

This module monitors the oxygen concentration in the Lab O305.

If the O2 concentration falls below 19%, a pre-alarm is triggered.
The yellow flashing light is switched on and an email is sent to techalarm-phys@unibas.ch and forwarded to the responsible persons. If the O2 concentration exceeds 19% again without having triggered the main alarm, the yellow continuous light switches off again.
Absender: LabWatch-161 / Room O305
Subject :  Pre-alarm: / U163 Critical oxygen concentration

Pre-alarm in Lab. O305
<t>
Oxygen concentration falls below 19%
Lab. O305 Tel.: +4161 207 37 32

More Infos on
https://labwatch.physik.unibas.ch/perswatch/161
Alarm Clear Subject : Cleared / O305 Oxygen concentration
Oxygen concentration im Lab. U163
<t>
Oxygen concentration is back in the normal range


If the O2 concentration falls below 17%, a main alarm is triggered.
The red flashing light and siren is switched on and an email is sent to techalarm-phys@unibas.ch and forwarded to the responsible persons. Even if the O2 concentration is back to normal, the main alarm must be acknowledged manually with the "SET" button. 
Absender: LabWatch-161 / Room O305
Subject :  Main alarm / O305 oxygen concentration too low

Main alarm in Lab. U163
<t>
Oxygen concentration is below 17%.
Lab. O305 Tel.: +4161 207 37 32

More Infos on
https://labwatch.physik.unibas.ch/perswatch/161

   Pre-alarm threshold value
  • O2-concentration < 19%
    yellow flashing light

    Main alarm thresholds
  • O2-concentration < 17%
    red flashing light and siren

By pressing the "SET" button on the Satellite-XT unit you can acknowledge the alarms.
An email with subject "Alarm Clear Oxygen Concentration" will be sent to techalarm@unibas.ch
If the O2 level is not within the normal range the alarm will be triggered again after 3 seconds.


The yellow flash light can also be triggered by an error message from the Satellite-XT device.

  • O2 concentration < 17% causes concentration problems
  • O2 concentration < 13% is life threatening